BCM 0000 A | Battery Controller Module

BCM 0000 A | Battery Controller Module
  • for extension of the FPA‑5000 with the Panel
  • Input voltage 20 V DC to 30 V DC 5 V DC ± 5%
  • Current consumption , Standby 31 mA (at 24 V DC) ; Fault 40 mA (at 24 V DC)

detail

ANI 0016 A | Annunciator Module

ANI 0016 A | Annunciator Module
  • The Annunciator Module has 16 red and 16 yellow LEDs for displaying the operating states of 16 definable detection points.
  • Input voltage 20 V DC to 30 V DC 5 V DC ± 5%
  • Max. current consumption , Standby (all LEDs off) 6 mA (at 24 V DC) ; All LEDs on 26 mA (at 24 V DC)

detail

LSN 0300 A | LSN improved Module 300 mA

LSN 0300 A | LSN improved Module 300 mA
  • This module allows the connection of an LSN loop with up to 254 LSN improved elements or 127 classic LSN elements, with a maximum line current of 300 mA
  • Line length up to 1600 m, depending on configuration and cable type
  • Line current up to 300 mA, depending on configuration and cable type

detail

LSN 1500 A | LSN improved Module 1500 mA

LSN 1500 A | LSN improved Module 1500 mA
  • This module allows the connection of an LSN loop with up to 254 LSN improved elements with a maximum line current of 1500 mA or with up to 127 classic LSN elements, with a maximum line current of 300 mA
  • Line length up to 3000 m, depending on configuration and cable type
  • Line current up to 1500 mA, depending on configuration and cable type

detail

FPE‑5000‑UGM | Module interface to UGM

 FPE‑5000‑UGM | Module interface to UGM
  • Communication Module is used to connect the fire panels FPA‑5000 and FPA‑1200 to a superordinate system like the UGM 2020, FAT 2002/RE and FSM‑2000

detail

CZM 0004 A | 4 Zone Conventional Module

CZM 0004 A | 4 Zone Conventional Module
  • CZM 0004 A is used to connect conventional peripherals and provides four monitored conventional lines
  • Connection of 2‑wire and 4‑wire conventional elements
  • Ready to go thanks to plug-and-play technology and pluggable terminal blocks

detail

IOS 0020 A | 20 mA Communication Module

IOS 0020 A | 20 mA Communication Module
  •  IOS 0020 A Communication Module has the following interfaces:
     - an S20 interfaces
     - an RS232 interface
  • The voice alarm system Plena can be connected via RS232.

detail

IOS 0232 A | RS232 Communication Module

IOS 0232 A | RS232 Communication Module
  • RS232 Communication Module can be used to connect two devices, e.g. voice alarm system Plena, a laptop or a printer, via two independent serial interfaces

detail

IOP 0008 A | Input/Output Module

 IOP 0008 A | Input/Output Module
  • IOP 0008 A Input/Output Module has eight independent digital inputs and eight open collector outputs for individual displays or flexible connection of various electrical devices.

detail

RML 0008 A | Relay Module

RML 0008 A | Relay Module
  • The module has eight change-over contact relays (type C) to provide potential-free output contacts.
  • Each of the eight relays has an NO (normally open) and an NC (normally closed) contact.
  • The maximum relay contact load is 30 V DC/1 A
  • 8 freely programmable relay outputs

detail